TR 5-450

It is typical that transient voltage surges from both external and internal sources directly affect the
performance and life expectancy of electronic equipment. Products having a printed circuit board inside, from electronic lighting ballasts to computer servers, may be susceptible to transient voltage surge damage. As microprocessors and components that make up this equipment grow smaller and faster with each new generation, their susceptibility to transient voltage surge damage becomes ever greater.

The full-featured GE Digital Energy TR Series SPD
(Surge Protective Device) line with its advanced monitoring,
disconnect and enclosure options has been designed to handle
the highest levels of surge activity found in the most demanding
commercial and industrial facilities. These units are ideal for both
new and retrofit applications where performance cannot be compromised.
GE engineers design and build surge protective devices (SPD’s) in our state-of-the-art lab and production
facilities. Extensive testing is performed at GE and a third-party test labs across North America.

Features & Benefits
Maximum Surge Current 3rd Party Tested per NEMA LS-1

  • 25 – 300kA per mode, maximum single impulse ratings.
  • All modes protection L-N, L-G, N-G, L-L.
  • “weak link” eliminated – entire TVSS surge path tested to ratings.

Robust MOV Technology

  • Industrial grade 40-48MM MOVs.
  • Industrial grade 40-48MM MOVs.
  • No “stacked” ratings of small electronic grade MOV arrays.
  • 25 – 200kA per mode devices use only (1 – 4) MOVs per mode.
  • 250 – 300kA devices – (3-6) 40-48MM MOVs.

Patented Thermal Fuse Technology
Industry Leading Longevity Characteristics

  • TR 7000 Series – 20,000 ANSI/IEEE Category C3 Impulses repetitive surges.
  • TR 5000 Series – Up to 5,000 ANSI/IEEE Category C3 impulses repetitive surges.
  • TR 7000 & 5000 Series – 5,000 ANSI/IEEE 500V, 2kA 10x1000micro sec. longwave repetitive surges.

Excellent Surge Clamping Performance

  • UL 1449, 2nd Edition Safety Standard(February 2007 revision), Suppressed Voltage Ratings (SVR) for all
  • levels of electrial distribution system including service entrance, distribution and point of use locations.

Compact and Durable Wall Mounted Design

  • Smaller size and weight makes easier installation in tight electrical rooms.
  • Heavy guage steel enclosures, painted and stainless designs, surface and flush configurations with
  • optional fiberglass on NEMA 4X.

Specifications

UL1449, 2nd edition (February 2007) listed.

UL 1283
CSA 22.2
ANSI / IEEE C62.21-1991(R1995)
ANSI / IEEE C62.45-2002
NEMA LS-1-1992 (R2000)
MIL-STD-220B
ANSI / NFPA 70B
NEC article 285

Product Scope

Per Mode 40kA
Per Phase 80kA
Surge Withstand 65 and 200kAIC
Voltage 120V to 240V
NEMA Ratings NEMA 1

Print